配电系统零线断线保护原理及现场应用
Distribution System Zero Line Break Protection Principle and Application

作者: 何智祥 * , 张慧 , 吴树钊 :广东电网有限责任公司佛山禅城供电局,广东 佛山; 柳春芳 , 陈增胜 , 梁唐杰 :佛山电力设计院有限公司,广东 佛山;

关键词: 三相配电系统零线断线负载不平衡位移电压Three-Phase Distribution System Zero Line Disconnection Load Unbalance Displacement Voltage

摘要:
当三相低压供电系统零线断线时,用户侧将出现中性点位移电压,可能引起设备及人身安全等事故。论文分析了三相配电系统零线断线时中性点位移电压和负载不平衡度的特征关系。基于零线断线时中性点出现位移电压但没有零线电流的特征,提出了带零线电流闭锁判据的识别零线断线的保护原理,并研究了零线断线保护的布点方案。

Abstract: When zero line disconnection occurs in three-phase distribution system, a displacement voltage will appear at the neutral point of client, which may cause the equipment and personal safety ac-cident. The relation between neutral point voltage and load unbalance is studied when zero line disconnection occurs in three-phase distribution system. The theoretical analysis shows that: zero sequence voltage appears at the neutral point and there is no zero sequence current when the zero line disconnection occurs. Based on this characteristic, a new method to detect zero line disconnection is proposed based on zero sequence voltage with zero line current blocking, and the layout scheme is studied.

文章引用: 何智祥 , 柳春芳 , 陈增胜 , 张慧 , 梁唐杰 , 吴树钊 (2015) 配电系统零线断线保护原理及现场应用。 输配电工程与技术, 4, 87-92. doi: 10.12677/TDET.2015.44009

参考文献

[1] 耿毅. 工业企业供电[M]. 北京: 冶金工业部出版社, 1985.

[2] 陈玉凤. 三项四线制供电系统中性点电位偏移的分析与监控[J]. 电工技术杂志, 2002(6): 44-46.

[3] 罗明. 对三相四线制供电系统中性点电位偏移的研究[J]. 电气开关, 2003, 41(3):36-37.

[4] 刘亦萍. 关于中性点电位偏移的分析与防护[J]. 上海第二工业大学学报, 2005(3): 31-36.

[5] 秦曾煌. 电工技术[M]. 北京: 高等教育出社, 1999: 157-164.

[6] 郑楚韬, 陈永杰. 三相四线制系统零线断线检测及保护研究[J]. 电气技术, 2008(8): 83-85.

[7] 朱雪凌. 三相四线制低压配电系统中零线断线过电压保护[J]. 华北水利水电学院学报, 2004, 25(3): 33-35.

[8] 王勇, 李志勇, 王永忠. 实现三相四线制供电系统中性线断线保护智能装置的研究[J]. 低压电器, 2011(5): 18-22.

分享
Top